Additional requirements for Current Transformers

Views : 844
Update time : 2024-08-14 09:52:16
5.5 Rated output 
5.5.201 Rated output values 
The standard values of rated output for measuring classes, class P and class PR are: 
2,5 – 5,0 – 10 – 15 and 30 VA. 
Values above 30 VA may be selected to suit the application. 
NOTE For a given transformer, provided one of the values of rated output is standard and associated with a standard accuracy class, the declaration of other rated outputs, which may be non-standard values, but associated with other standard accuracy classes, is not precluded. 
5.5.202 Rated resistive burden values 
Standard values for rated resistive burden in it for class TPX, TPY and TPZ current transformers are: 
The preferred values are underlined. The values are based on a rated secondary current of 1 A. For current transformers having a rated secondary current other than 1 A, the above values shall be adjusted in inverse ratio to the square of the current. 
NOTE For a given transformer, provided one of the values of rated resistive burden is standard and associated with a standard accuracy class, the declaration of other rated resistive burdens, which may be non-standard values, but associated with other standard accuracy classes, is not precluded. 
5.6 Rated accuracy class 
5.6.201 Measuring current transformers 
5.6.201.1 Accuracy class designation for measuring current transformers 
For measuring current transformers, the accuracy class is designated by the highest permissible percentage of the ratio error  at rated primary current and rated output. 
5.6.201.2 Standard accuracy classes 
The standard accuracy classes for measuring current transformers are: 0,1 – 0,2 – 0,2S – 0,5 – 0,5S – 1 – 3 – 5 
5.6.201.3 Limits of ratio error and phase displacement for measuring current transformers 
For classes 0,1 – 0,2 – 0,5 and 1, the ratio error and phase displacement at rated frequency shall not exceed the values given in Table 201 where the burden can assume any value from 25 % to 100 % of the rated output. 
For classes 0,2S and 0,5S the ratio error and phase displacement at the rated frequency shall not exceed the values given in Table 202 where the burden can assume any value from 25 % and 100 % of the rated output. 
For class 3 and class 5, the ratio error at rated frequency shall not exceed the values given in Table 203 where the burden can assume any value from 50 % to 100 % of the rated output. There are no specified limits of phase displacement for class 3 and class 5. 
For all classes, the burden shall have a power-factor of 0,8 lagging except that, when the burden is less than 5 VA, a power-factor of 1,0 shall be used, with a minimum value of 1 VA.  
NOTE In general the prescribed limits of ratio error and phase displacement are valid for any given position of an external conductor spaced at a distance in air not less than that required for insulation in air at the highest voltage for equipment.  
5.6.201.4 Extended burden range 
For all measuring classes, an extended burden range can be specified. The ratio error and phase displacement shall not exceed the limits of the appropriate class given in Table 201, Table 202 and Table 203 for the range of secondary burden from 1 VA up to rated output. The power factor shall be 1,0 over the full burden range. The maximum rated output is limited to 15 VA. 
5.6.201.5 Extended current ratings 
Current transformers of accuracy classes 0.1 to 1 may be marked as having an extended current rating provided they comply with the following two requirements: 
a) the rated continuous thermal current shall be the rated extended primary current.  
b) the limits of ratio error and phase displacement prescribed for 120 % of rated primary current in Table 201 shall be retained up to the rated extended primary current. 
The rated extended primary current shall be expressed as a percentage of the rated primary current. 
5.6.201.6 Instrument security factor 
An instrument security factor may be specified. 
Standard values are:  FS 5  and FS 10 
5.6.202 Protective current transformers
5.6.202.1 General 
Three different approaches are designated to define protective current transformers (see Table 204). In practice, each of the three definitions may result in the same physical realization.  
Related News
Read More >>
RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia
Jul .01.2026
RECT-66A current transformer supports energy meter installation in Bolivia, industrial power monitoring systems, and Class 0.3 billing accuracy systems for mining, hydro, commercial, and utility metering projects.
Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy
Jun .24.2026
HEYI KCT-24 current transformer is designed for electrical panel retrofit, energy meter connection, and power monitoring cabinet applications. Its split core design supports easy installation in Italian low voltage projects.
Current Transformer for Electrical Panels and Power Monitoring in Indonesia Current Transformer for Electrical Panels and Power Monitoring in Indonesia
Jun .17.2026
HEYI MSQ-30 current transformer supports energy meters, industrial power monitoring, low voltage panels, and power monitoring systems in Indonesia with stable current signals.
Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia
Jun .10.2026
HEYI CP series current transformer is designed for compact switchgear, DIN rail current transformer installation, and power monitoring cabinet applications in Russia, offering flexible mounting and reliable low-voltage measurement support.