Current transformer verification steps

Views : 448
Update time : 2024-11-15 08:43:51
(1) Connect the secondary load.

The current transformer should be connected to the specified upper or lower load.

Note that the lower load required by the regulations is 3.75VA (rated current 5A) and 1VA (rated current 1A).

If the user has requirements, the lower load is 1/4 of the rated load.

(2) Select the current ratio.

Unless the user has requirements, the current transformer is only tested for the ratio actually used.

If the user plans to change to another ratio during the calibration period, the user should ask the calibration agency to increase the ratio to be tested before the calibration.

(3) Select the current calibration point.

The current calibration point of the current transformer is selected according to Table 9.

When large current transformers (rated primary current 3kA and above) are tested in subsequent calibration and use, with the approval of the superior metrology administrative department, it is allowed to merge the 100% and 120% rated primary current calibration points into the actual maximum primary current point.

(4) Magnetic saturation margin test.

At present, the current range of the current transformer tester and load box is designed to be up to 120% of the rated current.

Therefore, the error at the 150% point or 200% point needs to be measured by extrapolation measurement method.

If the selected extrapolation starting point is not 20% of the rated current, but m%, the error at 150% of the rated current can be measured according to the following steps:

Assume that the rated secondary load of the current transformer is Z1, the secondary winding resistance and leakage reactance are Z2, and the error of the current transformer can be measured under the secondary load Z1, the current percentage point m%, and the secondary load 2Z1+Z2, the current percentage point 0.5m%, respectively, to obtain , 5 and force, 8.

Then measure the error of the current transformer under the secondary load (150/m)Z1+(150/m-1)Z2, the current percentage point m%.
Related News
Read More >>
SDH series Window Type Current Transformer - the precise core of global power monitoring and energy efficiency management SDH series Window Type Current Transformer - the precise core of global power monitoring and energy efficiency management
Apr .23.2026
The SDH series window type current transformer, as a high-precision component for low voltage and energy meters, is compatible with global power frequencies with a single model, ensuring energy monitoring and energy efficiency management.
Why is this residual current sensor an ideal current detection component for motor drive and industrial automation fields Why is this residual current sensor an ideal current detection component for motor drive and industrial automation fields
Apr .21.2026
HYCA leakage protection residual current sensor (current sensor) offers full current sensitivity and easy integration, outperforming hall sensors—ideal for motor drive and industrial automation.
Application scenarios of CT for motor protection relay in power generation, shipbuilding, and heavy industry industries Application scenarios of CT for motor protection relay in power generation, shipbuilding, and heavy industry industries
Apr .17.2026
The application scenarios of CT for motor protection in power generation, shipbuilding, and heavy industry include switchgear, MCC, and distribution boards.
The New Energy Landscape of Motor Giants: Why HYCA is Your Ideal Current Transformer for Switchgear Choice The New Energy Landscape of Motor Giants: Why HYCA is Your Ideal Current Transformer for Switchgear Choice
Apr .15.2026
The HYCA series current sensor is designed specifically for switchgear, integrating a switchable current transformer and motor current detection function, suitable for charging stations and industrial drive scenarios.