Determination of the turns ratio error

Views : 1001
Update time : 2024-10-07 15:50:10
The actual transformation ratio is affected by errors from three sources: 

a) the difference between the inverse of the turns ratio and the rated transformation ratio; 

b) the core exciting current (Ie); 

c) the currents which flow in the stray capacitances associated with the windings. 

In most cases, it is reasonable to assume that for a given secondary winding induced e.m.f. (Es), the error currents due to stray capacitances and core magnetization will maintain a constant value irrespective of the value of the primary energizing current. Es can theoretically be maintained at a constant value for a range of energizing currents, provided that the secondary loop impedance can be appropriately adjusted. For current transformers designed to be of the low-leakage reactance type, the secondary leakage reactance can be ignored and only the secondary winding resistance has to be considered. Thus, for any two currents  l's and I"s the basic equation defining the test requirement is 
given by    

where R is the actual resistance of the secondary winding. 

The respective error currents will be given by:  

whence: 

If I’s = 2I’’s, the turns ratio error is given by that. 

A test at rated current with minimum secondary connected burden, followed by a test at half rated current and suitable increase in secondary loop resistance, will usually give satisfactory results. 
Related News
Read More >>
DP Current Transformer for Energy Metering and Industrial Power Monitoring Applications in Jordan DP Current Transformer for Energy Metering and Industrial Power Monitoring Applications in Jordan
Jul .22.2026
DP current transformer delivers accurate energy metering and power monitoring for Jordan projects, supporting electrical panels, industrial applications, and low voltage systems with reliable performance and flexible installation.
Current Transformer for Switchboard Retrofit and Energy Metering Applications in Australia Current Transformer for Switchboard Retrofit and Energy Metering Applications in Australia
Jul .14.2026
KCT-24 current transformer is designed for Australian switchboard retrofit, energy metering and power monitoring applications. With split core installation, multiple output options and compact design, it helps engineers achieve accurate measurement without power interruption in electrical systems.
Current Transformer for Energy Metering and Industrial Power Monitoring Applications in Australia Current Transformer for Energy Metering and Industrial Power Monitoring Applications in Australia
Jul .10.2026
CP-62/40 current transformer delivers accurate measurement for Australian energy metering, electrical panels, and industrial power monitoring with compact design, flexible installation, and reliable performance.
Low Voltage Current Transformer for Energy Metering and Industrial Power Monitoring in India Low Voltage Current Transformer for Energy Metering and Industrial Power Monitoring in India
Jul .06.2026
Low voltage current transformer is used in energy metering, industrial power monitoring, manufacturing plants and automation production systems in India for accurate current measurement, stable monitoring and efficient energy management.