Determination of the turns ratio error

Views : 835
Update time : 2024-10-07 15:50:10
The actual transformation ratio is affected by errors from three sources: 

a) the difference between the inverse of the turns ratio and the rated transformation ratio; 

b) the core exciting current (Ie); 

c) the currents which flow in the stray capacitances associated with the windings. 

In most cases, it is reasonable to assume that for a given secondary winding induced e.m.f. (Es), the error currents due to stray capacitances and core magnetization will maintain a constant value irrespective of the value of the primary energizing current. Es can theoretically be maintained at a constant value for a range of energizing currents, provided that the secondary loop impedance can be appropriately adjusted. For current transformers designed to be of the low-leakage reactance type, the secondary leakage reactance can be ignored and only the secondary winding resistance has to be considered. Thus, for any two currents  l's and I"s the basic equation defining the test requirement is 
given by    

where R is the actual resistance of the secondary winding. 

The respective error currents will be given by:  

whence: 

If I’s = 2I’’s, the turns ratio error is given by that. 

A test at rated current with minimum secondary connected burden, followed by a test at half rated current and suitable increase in secondary loop resistance, will usually give satisfactory results. 
Related News
Read More >>
RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia
Jul .01.2026
RECT-66A current transformer supports energy meter installation in Bolivia, industrial power monitoring systems, and Class 0.3 billing accuracy systems for mining, hydro, commercial, and utility metering projects.
Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy
Jun .24.2026
HEYI KCT-24 current transformer is designed for electrical panel retrofit, energy meter connection, and power monitoring cabinet applications. Its split core design supports easy installation in Italian low voltage projects.
Current Transformer for Electrical Panels and Power Monitoring in Indonesia Current Transformer for Electrical Panels and Power Monitoring in Indonesia
Jun .17.2026
HEYI MSQ-30 current transformer supports energy meters, industrial power monitoring, low voltage panels, and power monitoring systems in Indonesia with stable current signals.
Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia
Jun .10.2026
HEYI CP series current transformer is designed for compact switchgear, DIN rail current transformer installation, and power monitoring cabinet applications in Russia, offering flexible mounting and reliable low-voltage measurement support.