Lift variation, stability and general technical requirements

Views : 542
Update time : 2024-12-04 16:41:24
3.2 Rise and fall variation

JJG313-2010】The difference in the error measurement results of the same current percentage point during the current rise and fall of the current transformer is called the rise and fall variation.

For the current transformer with an accuracy level of 0.2 or above used as a standard, the rise and fall variation shall not be greater than 1/5 of its error limit.

JJG314-2010】The difference in the error measurement results of the same voltage percentage point during the voltage rise and fall of the voltage transformer is called the rise and fall variation.

For the voltage transformer with an accuracy level of 0.2 or above used as a standard, the rise and fall variation shall not be greater than 1/5 of its error limit.

3.3 Stability

JJG313-2010】The error change of the current transformer shall not be greater than 1/3 of its error limit during the calibration cycle.

JJG314-2010】The error change of the voltage transformer shall not be greater than 1/3 of its error limit during the calibration cycle.
【Article Interpretation】As a measuring instrument, the value must be stable. If the deviation occurs between two calibrations, it will cause a value error.

If the standard instrument being tested is used for value transfer, it will cause value confusion.

Therefore, the measuring instrument must show a sufficiently good value stability at least in the interval between two calibrations.

Generally speaking, the value stability of electromagnetic transformers is relatively good, but if an error compensation circuit is added to the secondary side of the transformer, or an iron core material with unstable magnetic properties is used, it will affect the value stability of the transformer.

When determining the value stability index of the measuring transformer, the actual situation in my country should also be considered.

When revising the JJG313-1994 and JJG314-1994 regulations, the value stability requirements of the measuring transformer were specifically proposed, which should at least reach the level of general instruments, that is, one-third of the error limit.

4 General technical requirements

4.1 Appearance

JJG313-2010】The appearance of the current transformer should be intact, the terminal markings should be clear and complete, and the insulation surface should be dry and free of discharge marks.

【JJG314-2010】The appearance of the voltage transformer should be intact, and the terminal markings should be clear and complete.

The oil level of the oil-insulated transformer is correct, the gas-insulated transformer has normal filling pressure, the high-voltage bushing has no insulation defects, and there are no discharge marks on the high and low voltage insulation surfaces.

4.2 Insulation

【JJG313-2010】

4.2.1 The insulation resistance of the current transformer shall comply with the requirements of JB/T5472 Section 6.7

4.2.2 The power frequency insulation withstand voltage of the current transformer shall comply with the requirements of JB/T5472 Section 6.8.1.

【JJG314-2010】

4.2.1 The insulation resistance shall comply with the requirements of JB/T5473 Section 6.6.

4.2.2 The power frequency insulation withstand voltage shall comply with the requirements of JB/T5473 Section 6.7.1

4.2.3 The power frequency induction withstand voltage shall comply with the requirements of JB/T 5473 Section 6.7.2
Related News
Read More >>
RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia
Jul .01.2026
RECT-66A current transformer supports energy meter installation in Bolivia, industrial power monitoring systems, and Class 0.3 billing accuracy systems for mining, hydro, commercial, and utility metering projects.
Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy
Jun .24.2026
HEYI KCT-24 current transformer is designed for electrical panel retrofit, energy meter connection, and power monitoring cabinet applications. Its split core design supports easy installation in Italian low voltage projects.
Current Transformer for Electrical Panels and Power Monitoring in Indonesia Current Transformer for Electrical Panels and Power Monitoring in Indonesia
Jun .17.2026
HEYI MSQ-30 current transformer supports energy meters, industrial power monitoring, low voltage panels, and power monitoring systems in Indonesia with stable current signals.
Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia
Jun .10.2026
HEYI CP series current transformer is designed for compact switchgear, DIN rail current transformer installation, and power monitoring cabinet applications in Russia, offering flexible mounting and reliable low-voltage measurement support.