Protective current transformer classes for transient performance

Views : 1006
Update time : 2024-09-20 11:26:03

2B.2.3.3 Determination of the magnetizing inductance Lm  

The test procedure of 2B.2.3.2 shall be used. 

NOTE This formula differs slightly from the definition given in the preceding standard IEC 60044-6 (B4) due to the improved definition of saturation. 

2B.2.3.4 Determination of the error at limiting conditions  

The test circuit according to 2B.2.3.1 shall be used. 

For determination of the error at limiting conditions, the magnetizing current at the secondary linked flux shall be measured while increasing the flux.   

NOTE For TPZ current transformers, the accuracy is specified only for the a.c. component while, in the determination of the permissible value during indirect tests, it is also necessary to take the d.c. component of the exciting current into account. In the above equation, the d.c. component is represented by (Ktd – 1).  

2B.2.4 Capacitor discharge method  

The capacitor discharge method uses the charge of a capacitor for energizing the current transformer core from the secondary. The flux measurement is derived according to equation (1) given in 2B.2.1, where u(t) is  the voltage across the terminals. See Figure 2B.13. 

The capacitor is charged with a voltage sufficiently high to produce a secondary linked flux equal to or greater than the flux corresponding to Eal. See Figure 2B.13 and Figure 2B.14. 

At the time when it is reached, the peak value of the secondary exciting current shall be measured and shall not exceed the peak value of the exciting secondary current Îal.  

The secondary time constant Ts shall be determined by applying a voltage with a voltage-time integral corresponding to 90 % of Eal.

NOTE This definition of Ts does not conform with the definition in the above mentioned d.c. and a.c. methods. 

In determining the remanence factor KR, the integrated voltage with the corresponding current will determine a hysteresis loop. If the exciting current has been such that the saturation flux is reached, the flux value at zero crossing of the current is deemed to represent the remanent flux. 

2B.3 Direct test for determination of the error at limiting conditions 

2B.3.1 General 

The instantaneous error current can be measured in different ways. In all cases, the errors of the measuring system shall not exceed 10 % of the error limit corresponding to the class of the tested current transformer during the whole of the duty cycle.  

2B.3.2 Direct test 

Class TPX current transformers shall be demagnetized before the direct test because of the high remanence factor. It may be necessary to demagnetize class TPY current transformers if the remanence factor KR is not negligible.  

Two direct tests shall be performed at rated frequency and with rated secondary burden: 

a) The rated primary short-circuit current at rated frequency is applied without any offset. The a.c. component of the instantaneous error is measured and shall be in accordance with the theoretical value.  

b) To verify that the current transformer meets the accuracy requirements of the specified duty cycle, the following test shall be performed: 

The rated primary short-circuit current at rated frequency is applied with the required offset. For specified values of primary time constant up to 80 ms, the test is performed in the specified accuracy limiting condition (specified duty cycle). The primary time constant shall not deviate by more than 10 % from the specified value. 
Related News
Read More >>
RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia RECT-66A Extended Range Current Transformer for Reliable Energy Metering in Bolivia
Jul .01.2026
RECT-66A current transformer supports energy meter installation in Bolivia, industrial power monitoring systems, and Class 0.3 billing accuracy systems for mining, hydro, commercial, and utility metering projects.
Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy Current Transformer for Electrical Panel Retrofit and Power Monitoring in Italy
Jun .24.2026
HEYI KCT-24 current transformer is designed for electrical panel retrofit, energy meter connection, and power monitoring cabinet applications. Its split core design supports easy installation in Italian low voltage projects.
Current Transformer for Electrical Panels and Power Monitoring in Indonesia Current Transformer for Electrical Panels and Power Monitoring in Indonesia
Jun .17.2026
HEYI MSQ-30 current transformer supports energy meters, industrial power monitoring, low voltage panels, and power monitoring systems in Indonesia with stable current signals.
Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia Current Transformer for Compact Switchgear and DIN Rail Power Monitoring in Russia
Jun .10.2026
HEYI CP series current transformer is designed for compact switchgear, DIN rail current transformer installation, and power monitoring cabinet applications in Russia, offering flexible mounting and reliable low-voltage measurement support.