The HYCA-08-MD is a high-performance Residual Current Detection Module (RDC-MD) developed by Wenzhou Heyi Electrical Co., Ltd. Designed for earth leakage protection in electrical systems, this product complies with IEC 62752 and IEC 62955 standards while meeting RoHS/REACH environmental directives. With a theoretical design life exceeding 20 years, it serves as a critical safety component for electric vehicle charging stations and power conversion equipment.![]()
Power Characteristics
Single power supply: 4.85-5.15VDC (nominal 5V)
Low power design: <110mW
Power ripple requirement: ≤150mV
Output Characteristics
Logic level output: Low level ≤0.6V, High level ≥4.2V
TRIP signal: Transitions from low to high when leakage current exceeds threshold
Status signal: Outputs 1kHz PWM waveform with 50% duty cycle during normal operation
Environmental Robustness
Operating temperature range: -40℃ to +85℃
Storage temperature range: -20℃ to +65℃
Operational altitude: <4000m
Humidity tolerance: ≤95%RH
| Waveform Type | Frequency | Min Trip Current(mA) | Typ Trip Current(mA) | Max Trip Current(mA) |
|---|---|---|---|---|
| S-DC | - | 3 | 4.5 | 6 |
| 2PDC | - | 3.5 | 5 | 7 |
| 3PDC | - | 3.1 | 4.5 | 6.2 |
For 6mA S-DC leakage current:
Typical response: 120ms
Maximum response: 1000ms
For 200mA high current scenarios:
All waveform types respond within 50-100ms
The module features PCB mounting with a standard application circuit including:
Power filtering
Core detection module
Signal conditioning
Control electronics interface
Pin definition:
VDD: Power input (5V±5%)
TRIP: Fault output signal
GND: Power ground
Status: Monitoring output
TEST: Self-test input
HYCA-08-MD incorporates comprehensive self-test capabilities:
Zero-drift Calibration: Grounding TEST pin triggers automatic zero-point calculation and calibration value storage
Simulation Test: Generates internal 6.53mADC simulated leakage current for functional verification
Timing Requirements:
Power ramp rate ≤5ms/V
Self-test command duration: 50-100ms
Calibration completion: ≈200ms
Total test cycle: ≈1.5s
Critical Note: Main circuit must be disconnected during self-test to prevent actual leakage current interference.
EV Charging Systems
Safety protection for public charging stations against insulation faults
Power Conversion Equipment
Leakage current monitoring for inverters and converters
Smart Grid Systems
Ground fault detection in power distribution networks
Dual-Threshold Design
Trip threshold (IAT) at 100% of typical value, reset threshold (IAX) at 55% prevents signal oscillation
Wide Detection Range
Capable of detecting leakage currents from mA to A levels
Power Monitoring
Built-in supply voltage monitoring with automatic status output switching below 4.69V
Environmental Durability
Validated across -40℃ to +85℃ temperature range
The HYCA-08-MD Residual Current Monitoring Unit delivers high precision, reliability, and comprehensive self-protection for modern power electronic systems. Particularly in the rapidly evolving EV charging infrastructure, this product effectively prevents personal injury and equipment damage caused by insulation faults, making it an ideal choice that meets international safety standards.